Products Characteristics

The ABT Enduro TFT designed for dual purpose high rate and floating applications.

  •  Designed service life: 10 years (20oC)
  •  High current discharge performance and high power output
  •  Low self-discharge rate: ≤3% (20oC) monthly on average
  •  Patented terminal design to ensure reliable leakage-proof performance
  •  Easy installation and handling
  •  Gas pipe designed
  •  High products consistency
  •  Safety and reliable leakage-proof
  •  Operating in wide ambient temperature range:-15oC~45oC

Applications

 

 

Battery Construction

 

Technical Features

Sealed Construction
Unique construction and sealing technique ensures no electrolyte leakage from case or terminalsl

AGM Separator Design
Low resistance microporous glass fibre separator .The electrolyte is absorbed within this material.

Gas Recombination Efficiency
ABT Enduro TFT batteries incorporate a built-in design that controls gas generation and provides recombination of more than 99% of gas generation during float usages.

Low Pressure Valve Regulated System
All ABT Enduro TFT batteries are equipped with safety release valves , designated to operate between 1.4 and 5 psi and automatically close . Hence there is never an excessive accumulation of gas within the battery .

Maintenance Free Operation
There is no need to check specific gravity of the electrolyte or add water to ABT Enduro TFT batteries during float service life.

Terminals
Front terminals M6 and M8 thread inserted for easy installation and maintenance.

 